Go modbus stack
Description
This package is a go implementation of the modbus protocol. It aims to provide a simple-to-use, high-level API to interact with modbus devices using native Go types.
Both client and server components are available.
The client supports the following modes:
- modbus RTU (serial, over both RS-232 and RS-485),
- modbus TCP (a.k.a. MBAP),
- modbus TCP over TLS (a.k.a. MBAPS or Modbus Security),
- modbus TCP over UDP (a.k.a. MBAP over UDP),
- modbus RTU over TCP (RTU tunneled in TCP for use with e.g. remote serial ports or cheap TCP to serial bridges),
- modbus RTU over UDP (RTU tunneled in UDP).
Please note that UDP transports are not part of the Modbus specification. Some devices expect MBAP (modbus TCP) framing in UDP packets while others use RTU frames instead. The client support both so if unsure, try with both udp:// and rtuoverudp:// schemes.
The server supports:
- modbus TCP (a.k.a. MBAP),
- modbus TCP over TLS (a.k.a. MBAPS or Modbus Security).
A CLI client is available in cmd/modbus-cli.go and can be built with
$ go build -o modbus-cli cmd/modbus-cli.go
$ ./modbus-cli --help
Getting started
$ go get github.com/simonvetter/modbus
Using the client
import (
"github.com/simonvetter/modbus"
)
func main() {
var client *modbus.ModbusClient
var err error
// for a TCP endpoint
// (see examples/tls_client.go for TLS usage and options)
client, err = modbus.NewClient(&modbus.ClientConfiguration{
URL: "tcp://hostname-or-ip-address:502",
Timeout: 1 * time.Second,
})
// note: use udp:// for modbus TCP over UDP
// for an RTU (serial) device/bus
client, err = modbus.NewClient(&modbus.ClientConfiguration{
URL: "rtu:///dev/ttyUSB0",
Speed: 19200, // default
DataBits: 8, // default, optional
Parity: modbus.PARITY_NONE, // default, optional
StopBits: 2, // default if no parity, optional
Timeout: 300 * time.Millisecond,
})
// for an RTU over TCP device/bus (remote serial port or
// simple TCP-to-serial bridge)
client, err = modbus.NewClient(&modbus.ClientConfiguration{
URL: "rtuovertcp://hostname-or-ip-address:502",
Speed: 19200, // serial link speed
Timeout: 1 * time.Second,
})
// note: use rtuoverudp:// for modbus RTU over UDP
if err != nil {
// error out if client creation failed
}
// now that the client is created and configured, attempt to connect
err = client.Open()
if err != nil {
// error out if we failed to connect/open the device
// note: multiple Open() attempts can be made on the same client until
// the connection succeeds (i.e. err == nil), calling the constructor again
// is unnecessary.
// likewise, a client can be opened and closed as many times as needed.
}
// read a single 16-bit holding register at address 100
var reg16 uint16
reg16, err = client.ReadRegister(100, modbus.HOLDING_REGISTER)
if err != nil {
// error out
} else {
// use value
fmt.Printf("value: %v", reg16) // as unsigned integer
fmt.Printf("value: %v", int16(reg16)) // as signed integer
}
// read 4 consecutive 16-bit input registers starting at address 100
var reg16s []uint16
reg16s, err = client.ReadRegisters(100, 4, modbus.INPUT_REGISTER)
// read the same 4 consecutive 16-bit input registers as 2 32-bit integers
var reg32s []uint32
reg32s, err = client.ReadUint32s(100, 2, modbus.INPUT_REGISTER)
// read the same 4 consecutive 16-bit registers as a single 64-bit integer
var reg64 uint64
reg64, err = client.ReadUint64(100, modbus.INPUT_REGISTER)
// read the same 4 consecutive 16-bit registers as a slice of bytes
var regBs []byte
regBs, err = client.ReadBytes(100, 8, modbus.INPUT_REGISTER)
// by default, 16-bit integers are decoded as big-endian and 32/64-bit values as
// big-endian with the high word first.
// change the byte/word ordering of subsequent requests to little endian, with
// the low word first (note that the second argument only affects 32/64-bit values)
client.SetEncoding(modbus.LITTLE_ENDIAN, modbus.LOW_WORD_FIRST)
// read the same 4 consecutive 16-bit input registers as 2 32-bit floats
var fl32s []float32
fl32s, err = client.ReadFloat32s(100, 2, modbus.INPUT_REGISTER)
// write -200 to 16-bit (holding) register 100, as a signed integer
var s int16 = -200
err = client.WriteRegister(100, uint16(s))
// Switch to unit ID (a.k.a. slave ID) #4
client.SetUnitId(4)
// write 3 floats to registers 100 to 105
err = client.WriteFloat32s(100, []float32{
3.14,
1.1,
-783.22,
})
// write 0x0102030405060708 to 16-bit (holding) registers 10 through 13
// (8 bytes i.e. 4 consecutive modbus registers)
err = client.WriteBytes(10, []byte{
0x01, 0x02, 0x03, 0x04,
0x05, 0x06, 0x07, 0x08,
})
// close the TCP connection/serial port
client.Close()
}
Using the server component
See:
- examples/tcp_server.go for a modbus TCP example
- examples/tls_server.go for TLS and Modbus Security features
Supported function codes, golang object types and endianness/word ordering
Function codes:
- Read coils (0x01)
- Read discrete inputs (0x02)
- Read holding registers (0x03)
- Read input registers (0x04)
- Write single coil (0x05)
- Write single register (0x06)
- Write multiple coils (0x0f)
- Write multiple registers (0x10)
Go object types:
- Booleans (coils and discrete inputs)
- Bytes (input and holding registers)
- Signed/Unisgned 16-bit integers (input and holding registers)
- Signed/Unsigned 32-bit integers (input and holding registers)
- 32-bit floating point numbers (input and holding registers)
- Signed/Unsigned 64-bit integers (input and holding registers)
- 64-bit floating point numbers (input and holding registers)
Byte encoding/endianness/word ordering:
- Little and Big endian for byte slices and 16-bit integers
- Little and Big endian, with and without word swap for 32 and 64-bit integers and floating point numbers.
Logging
Both client and server objects will log to stdout by default. This behavior can be overriden by passing a log.Logger object through the Logger property of ClientConfiguration/ServerConfiguration.
TODO (in no particular order)
- Add RTU (serial) support to the server
- Add more tests
- Add diagnostics register support
- Add fifo register support
- Add file register support
Dependencies
- github.com/goburrow/serial for access to the serial port (thanks!)
License
MIT.